Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2026 Residential Zoning APPROVED
04/13/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/02/2026 Light Residential Building Review (OIP) - Standard REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov

Please resubmit addressing the following comment:
1) Please clarify if the NEMA receptacle will be 50A or 60A, plans show 50A on PV 06 and 60A on PV10.
2) Demonstrate how the EVSE circuit will be GFCI protected. 625.54
3) A Surge Protection Device (SPD) is required for all Service Panel replacements. This requirement can be satisfied by providing the manufacturer’s specifications for the SPD to verify that it is UL listed and code compliant E606.5 NEC 230.67