| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/01/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/01/2025 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | Permit Review TC-RES-0425-02287 (2517 W CALLE PARAISO TUCSON, AZ 85745) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide an updated Plan and a written response letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response letter addressing the comments below maybe be delayed until the response letter is received. For questions: Building_Official@tucsonaz.gov 1. For the given pipe length and 199,000 BTUs, the pipe segment running to the water heater is undersized and requires to be a minimum of 1'' per Table G2413.4(7). 2. Minimum burial depth 18'' for non-metallic pipe, G2415.12 3. Yellow tracer wire required for non-metallic pipe, G2415.17.3 4. See drawing for markups. |
||