Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-RES-0425-02270
Parcel: 141331270

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-0425-02270
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/07/2025 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT Permit Review TC-RES-0425-02270 (10591 E OTTOMAN DR TUCSON, AZ 85747)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response letter addressing the comments below maybe be delayed until the response letter is received. For additional questions: Building_Official@tucsonaz.gov

1. Include electrical circuiting information for the new HVAC unit, including breaker size, conductor type and size. Provide the main panel rating.

2. Provide electrical load calculations for verifying the service panel size is sufficient for the additional loads, E3602.2.

3. Provide/update HVAC demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1.
05/06/2025 PDSD Application Completeness Express REVIEW COMPLETED