Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL POOL v.1
Permit Number - TC-RES-0425-02268
Review Name: RESIDENTIAL POOL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/17/2025 | Site Engineering | NOT REQUIRED | |||
| 05/17/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/12/2025 | Residential Building | REQUIRES RESUBMIT | Please show the overhead electrical line from the pole to the house and indicate the distance between the pool and the drop of said overhead line. Per E4203.6 Overhead conduction clearances: Except where installed with the clearances specified in Table E4203.6, the following parts of pools and outdoor spas and hot tubs shall not be placed under existing service-drop conductors, overhead service conductor, or any other open overhead wiring; nor shall such wiring be installed above the following: 1.Pools and the areas extending not less than 10 feet, (3048 mm) horizontally from the inside of the walls of the pool. Vertically it must be 22.5' from the water. |
||
| 05/16/2025 | Site Zoning | REQUIRES RESUBMIT | FROM: PDSD Zoning Review Section PROJECT: TC-RES-0425-02268 4710 E CECELIA ST. – R-1 Inground pool (1st Review) TRANSMITTAL DATE: May 16, 2025 This comment was not addressed. Comment: Provided a detailed comment response letter with your submittal that clearly shows how you have addressed all comments with your next submittal. This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9. 1. The porch shown on the plan located near the southeast corner of the property appears on aerial photos sometime after 2020. Zoning was not able to find approved permit documents for this structure. As it appears this structure is greater than 200 sq. ft. a separate building permit will need to be submitted and approved prior to approval of this pool permit. The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 04/30/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |