Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.2
Permit Number - TC-RES-0425-02257
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/02/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/02/2025 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | Permit Review TC-RES-0924-05536 (801 W ALTURAS ST TUCSON, AZ 85705) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide an updated Plan and a written response letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response letter addressing the comments below maybe be delayed until the response letter is received. 1. For the given pipe length 60' and total demand, 279,000 BTUs, the main pipe running from meter to all attached appliances is still undersized. Pipe size per Table should be a minimum of 1 1/4'' to meet the demand of all gas fire appliances G2413.4(1). 2. In addition to providing pipe size for each segment, pipe lengths for each segment is also required. For questions: Building_Official@tucsonaz.gov |
||
| 05/02/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |