Permit Number: TC-RES-0425-02238
Parcel: 113060290

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0425-02238
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/29/2025 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT Please resubmit the following information for review.
1. HVAC- Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D.
2. Provide total demand from all appliances, G2413.2.
Provide a gas piping plan showing the connection from the meter to ALL attached appliances. Include pipe size, type, and length. Show connection, lengths, and sizes, from gas meter to ALL gas appliances. Modifications to the gas system requires the submission of a gas pipeline template (or equivalent), G2401.1, G2413.1, R301.1.
Gas Lines- Use Table G2413.4(1) (Metallic Pipe) to calculate correct required pipe sizes.
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/gas_handout_2018_irc_2019.2.4.pdf
building_official@tucsonaz.gov
04/29/2025 PDSD Application Completeness Express REVIEW COMPLETED