Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0425-02238
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/29/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/29/2025 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | Please resubmit the following information for review. 1. HVAC- Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D. 2. Provide total demand from all appliances, G2413.2. Provide a gas piping plan showing the connection from the meter to ALL attached appliances. Include pipe size, type, and length. Show connection, lengths, and sizes, from gas meter to ALL gas appliances. Modifications to the gas system requires the submission of a gas pipeline template (or equivalent), G2401.1, G2413.1, R301.1. Gas Lines- Use Table G2413.4(1) (Metallic Pipe) to calculate correct required pipe sizes. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/gas_handout_2018_irc_2019.2.4.pdf building_official@tucsonaz.gov |
||
| 04/29/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |