Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-RES-0425-02236
Parcel: 11803308B

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0425-02236
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/29/2025 Site Engineering Express PENDING ASSIGNMENT
04/29/2025 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT Permit Review TC-RES-0425-02236 (2231 W SAN MARCOS BL TUCSON, AZ 85713)

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide an updated Plan and a written response letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response letter addressing the comments below maybe be delayed until the response letter is received.

1. Note and specify piping materials (Black Iron, Gas line PEX, etc.), G2412.9.

2. Size the pipe based on the length from the meter to the farthest attached appliance and max total demand of all attached appliances using Table G2413.4(1) (Metallic Pipe), Table G2413.4(7) Polyethylene Plastic Pipe. Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1.

3. You're gas template/drawing is missing typical appliance input (BTU'S) and total demand.

See drawing for markups For questions: Building_Official@tucsonaz.gov
04/29/2025 PDSD Application Completeness Express REVIEW COMPLETED