Permit Number - TC-RES-0425-02186
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/25/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/25/2025 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | ACTIVITY NO. TC-RES-0425-02186 ADDRESS/PARCEL: (2750 E MANCHESTER ST TUCSON, AZ 85716) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter. Comments: 1. Please show the location of the EV Receptacle in the carport. In locations where electrical equipment is likely to be exposed to physical damage, enclosures or guards shall be so arranged and of such strength as to prevent such damage. - NEC 110.27 - (B) 2. Highlight the EV charger input on the electrical load calculations 3. Show wiring methods from EV charging station to main service panel. If wiring across roof, notate the following on the provided plans: The bottom of the conduit shall be a minimum of 7/8” above the roof surface, NEC 310.15(B)(3)(c). 4. Provide GFCI protection for the new EV charging receptacle per NEC 625.54. 5. Please resubmit |
||