04/28/2025 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT Permit Review TC-RES-0425-02159 (4549 E PATRICIA ST TUCSON, AZ 85712)

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response letter addressing the comments below maybe be delayed until the response letter is received. For additional questions: Building_Official@tucsonaz.gov

1. Include electrical circuiting information for the new HVAC unit, including breaker size, conductor type and size. Provide the main panel rating.

2. Show a GFCI receptacle outlet on the same level within 25’ of exterior HVAC equipment, E3901.12.

3. Provide electrical load calculations for verifying the service panel size is sufficient for the additional loads, E3602.2.

4. Make sure all files have the corresponding address 4549 E Patricia St. files that contain a different address will require another resubmittal.