Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.1
Permit Number - TC-RES-0425-02063
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/27/2025 | Site Zoning - Standard | APPROVED | |||
| 06/04/2025 | Site Engineering - Standard | NOT REQUIRED | |||
| 06/04/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/25/2025 | Addressing Validation | REQUIRES RESUBMIT | The main residence and the ADU have to both be labeled/marked on the construction plans. Please resubmit the construction plans to reflect unit numbers, and submit a change of address request to correct the address on the permit. For questions: Building_Official@tucsonaz.gov |
||
| 05/22/2025 | Residential Building - Standard | REQUIRES RESUBMIT | TC-RES-0425-02063 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. GENERAL REQUIREMENTS: The City of Tucson adopted the 2018 IRC with amendments and building ordinances for all dwellings. Provide a response letter addressing each comment with location of change on the plans. Submit separate letter and plan set files. PLANS: 1. Show compliance with R310 providing egress from bedrooms with minimum net clear opening height of 24”. Update W04 size. MECHANICAL PLANS: 1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation with controlled exhaust, R303.4; N1103.6 & M1505.4. Identify the device model number providing an adjustable setting and note the minimum continuous setting. A two or three-bedroom dwelling under 1501 SF requires a 45 CFM continuous setting. Extend general statement of note #4 with the minimum required setting for this dwelling. INTERNATIONAL ENERGY CONSERVATION CODE: 1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans. If you have any questions, please contact: Ken Van Karsen PDSD-Residential@tucsonaz.gov City of Tucson Residential Plan Review Submit a corrected plan set at https://www.tucsonaz.gov/pdsd |
||
| 04/25/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |