Permit Number: TC-RES-0425-02038
Parcel: 126041690

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0425-02038
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2025 Site Engineering - Standard NOT REQUIRED
05/19/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/14/2025 Residential Building - Standard REQUIRES RESUBMIT TC-RES-0425-02038
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance. The plans require sufficient detail for demonstrating minimum building code compliance for passing all progress inspections.

Note the 2018 IRC reference on the plans.

Provide a response letter addressing each comment with location of change on the plans. Submit separate letter and plan set files.

PLANS:

1. Show the dimensions of the altered carport and proposed foyer and porch addition on the foundation plan sheet A-3, R106.1.1.

SECTIONS - DETAILS:

1. Provide a wall section detail with (#4 rebar) reinforced reinforced foundations for anchoring exterior framed (insulated) walls with pressure treated sills including ½” anchor bolts with 7” embedment, R403.1.6.
2. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5). The weep screed may extend with a minimum clearance 4” above grade or 2” above paved areas, R703.7.2.1.
3. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. Attic space outside of the thermal barrier requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2 or an unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Identify the ventilation requirements and insulation types for complying with the condensation control issues.

PLUMBING PLANS:

1. Show an appropriate yard pipe size on sheet A-11 & A-12, P2903.7. A 3” pipe is not feasible for a residential building.
2. Show an appropriate proposed bathroom branch pipe size on sheet A-11, P2903.7. A ½” cold water pipe is undersized for the demand.

MECHANICAL PLANS:

1. Provide demand calculations in accordance with Manual J standards, M1401.3, M1601.1.

ELECTRICAL PLANS:

1. Clarify if the 200 AMP panel is existing or proposed, R106.1.1.
2. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3. These circuits are separate from the refrigerator and dishwasher circuits. Also add a receptacle at the countertop above the dishwasher.
3. Interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights, and smoke detectors require combination type arc-fault circuit interrupters, E3902.16. Complete the “AF” notation entries on the panel schedule.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits. Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
----------------------
05/19/2025 Site Zoning - Standard REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-RES-0425-02038
829 N CATALINA Av. – R-1
Convert Carport to Bedroom with Bathroom and Foyer Addition (1st Review)

TRANSMITTAL DATE: May 19, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9.

1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Plan-Examples/Plot-Plan-Example. to include but not limited to:
a. The plot plan shall show what is proposed.
b. The plot plan shall be drawn at an engineering scale, i.e. 1” = 10, 1” = 20’.
c. Provide a dimension from the centerline of Catalina Ave. to the face of curb and from face of curb to the east property line.
d. Provide applicable perimeter yard setback dimensions from all proposed work to the applicable property lines.
e. The lot coverage calculation is not correct. Per UDC Article 6.4.3.B.3.b Vehicular use areas, measured within the outside edges of any area allocated to vehicle use, whether improved or unimproved are included in the lot coverage.
f. The provided site plan shows sidewalk along Catalina Ave. but based on aerial photos there are no sidewalks along Catalina Ave..
g. The FRONT SETBACK + 20’-0” OR 2/3 H”, listed on the site plan is not correct. Review UDC Article 6.4.5.C.1.a and provide the correct street perimeter yard setback.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
04/17/2025 PDSD Application Completeness Express REVIEW COMPLETED