Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0425-01814
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/09/2025 | Site Engineering - Standard | NOT REQUIRED | |||
| 05/09/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/06/2025 | Light Residential Building Review (OIP) - Standard | REQUIRES RESUBMIT | Permit Review TC-RES-1224-07063 (3726 E DOVER SV TUCSON, AZ 85706). Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). 1. Provide ESS and PV backfeed interconnection at the main panel in compliance with NEC 706.9(E) & 705.12. 2. Provide ESS disconnecting means within sight, 706.7(A) of the ESS and within 5 feet, 706.7(E)(1) &(2). Building_official@tucsonaz.gov |
||
| 04/10/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |