Permit Number: TC-RES-0425-01781
Parcel: 116210760

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0425-01781
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2025 Site Engineering - Standard NOT REQUIRED
05/19/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/14/2025 Residential Building - Standard REQUIRES RESUBMIT TC-RES-0425-01781
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments and building ordinances for all dwellings. Show the current code reference on the plans.

Provide a response letter addressing each comment with location of change on the plans. Submit separate letter and plan set files.

GENERAL COMMENTS :

1. All plans submitted for a newly constructed one- or two-family dwelling after June 1, 2010, must provide gray water utilization or preparation, Ordinance #10579/11089 revised July 9, 2013. Include two clothes washer standpipes, one with an above grade stub-out, and one to the building drain; also provide gray drain-line discharge of all second story bathing fixtures through an exterior-wall drop for future gravity distribution. Include an aliened purple colored 2” or 3” vertical drop to a cleanout cap 2’ above grade. Remove the gray water detail for below grade plumbing on sheet P1.0 and use the appropriate detail at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Water-Energy-Conservation Gray Water Illustrations

PLANS:

1. Indicate the direction of slope for the garage slab, R309.1.

SECTIONS - DETAILS:

1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. Clarify the ceiling/roof insulation detail showing the air-impermeable rigid insulation material adhered to either side of the roof sheathing along with the batt insulation. Update keynote #14 on sheet A4.0 and detail #6 on A7.0.

PLUMBING PLANS:

1. Tucson Water Department limits flow rates for each water meter size in compliance with P2903.7. Show an appropriate 1” yard pipe and show the water meter size. Also, update the yard pipe size on the plan sheet P1.0 and keynote #3.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation with controlled exhaust, R303.4; N1103.6 & M1505.4. Identify the device model type providing an adjustable setting and note the minimum continuous setting or intermittent operation. A six-bedroom dwelling greater than 3000 SF requires a 105 CFM continuous setting (two devices may be used). A two- or three-bedroom dwelling greater than 1500 SF requires a 60 CFM continuous setting. Update the Ventilation Schedule.
2. Provide demand calculations in accordance with Manual J standards, M1401.3, M1601.1.

ELECTRICAL PLANS:

1. Smoke alarms are required in each sleeping area, R314.3. Show in bedrooms #11 and 14.

OUTDOOR LIGHTING CODE

1. . Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
05/19/2025 Site Zoning - Standard REQUIRES RESUBMIT To secure this neighbor’s setback waiver the following statement must be provided on the plot plan and be signed and dated by the adjacent property owner(s):
My Name is____________________ and I am the owner of the property located at_______________________. I have reviewed the site plan and I have no objection to structure being located or constructed________ feet from the property line as depicted on the site plan.

Signature: _____________________________

Date: _________________________________
If you are not able to secure this waiver a Design Development Option (DDO) to reduce the setback will need to be submitted and approved. DDO application and requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. If you have questions about the DDO application or process please contact Georgia Pennington at Georgia.Pennington@tucsonaz.gov”.
04/17/2025 Addressing Validation REVIEW COMPLETED The address assigned to the 2nd unit is 1133 W Cedar St
04/17/2025 PDSD Application Completeness Express REVIEW COMPLETED