Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.1
Permit Number - TC-RES-0425-01713
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/06/2025 | Site Engineering - Standard | NOT REQUIRED | |||
| 05/09/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/01/2025 | Residential Building - Standard | REQUIRES RESUBMIT | TC-RES-0425-01713 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance. The plans require sufficient detail for demonstrating minimum building code compliance for passing all progress inspections. Note the 2018 IRC reference on the plans. The plans may require additional changes for showing 2018 IRC compliance of construction performed without a permit. Provide plans showing all changes after the last completed permit and proposed alterations. Provide construction plans with sheet numbering in a single PDF file. Provide a response letter addressing each comment with location of change on the plans. Submit separate letter and plan set files. Provide a clear and concise construction plan set. Sample drawings are available for understanding details. Sample plans at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits SECTIONS – DETAILS for Enclosed Carport: 1. Provide a wall section detail with (#4 rebar) reinforced 12” x 12” reinforced foundations for anchoring exterior framed (insulated) walls with pressure treated sills including ½” anchor bolts with 7” embedment, R403.1.6. 2. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5). The weep screed may extend with a minimum clearance 4” above grade or 2” above paved areas, R703.7.2.1. 3. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. PLUMBING PLANS: 1. Show each gas pipe segment sized in conformance with Table G2413.4(1). Existing gas pipes may require upgrading with this system alteration. MECHANICAL PLANS: 1. Show the HVAC (heating & cooling) system size and location accordance with M1401.3, M1601.1. 2. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D. ELECTRICAL PLANS: 1. Designate the circuit number at the location of each light fixture, receptacle, appliance, and equipment disconnect switch, R106.1.1. 2. Provide a panel schedule showing all circuits, E3702.2. 3. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2. 4. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3. 5. Interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights, and smoke detectors require combination type arc-fault circuit interrupters, E3902.16. Add notation to plans. OUTDOOR LIGHTING CODE 1. Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3. If you have any questions, please contact: PDSD-Residential@tucsonaz.gov City of Tucson Residential Plan Review Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services ---------------------- |
||
| 05/09/2025 | Site Zoning - Standard | REQUIRES RESUBMIT | PDSD TRANSMITTAL FROM: Jeffrey W. Cassidy, Planner Planning & Development Services Department – Zoning Review Section PROJECT: TC-RES-0425-01713 – Residential Building – Remodel SFR and Enclose Carport 229 W Jacinto St Tucson, AZ 85705 (R-3 Zoning) Building Plan Review -1st Review TRANSMITTAL DATE: May 09, 2025 This site is in the R-3 zone (Unified Development Code (UDC) Article 4.7.12). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.6. Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued. SCOPE OF REVIEW: The scope of this plan review covers zoning, use(s), legal description, adjacent properties, setbacks (building or wall heights), dimensional standards, property permitting history, density (units/lot size), and lot calculation (enclosed building and structure, parking, and driveway versus overall lot size) requirements. All code references are to the Tucson, AZ Unified Development Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Correct the following site plan and provide missing sheets, as noted in the comments below, along with a detailed response letter indicating responses to the review comments. PLANS: 1. COMMENT: Clarify scope of work. This was filed as ‘Renovate SFR and Enclose Carport’ when the drawings propose a duplex. It appears any drawings related to any renovation (existing conditions, demolition, elevations) and how that correlates to the proposed scope) are missing. 2. COMMENT: The site plan provided is inaccurate and incomplete. Provide a site plan that meets the requirements show in the plot plan example at the following link: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Plan-Examples/Plot-Plan-Example 3. COMMENT: The shared driveway is not part of the parcel and need not be depicted. 4. COMMENT: Additional comments may be forthcoming on the next review based on the proposed use for the addition and applicable use specific standards. Please contact the zoning reviewer if you have any questions: Jeffrey W Cassidy jeffrey.cassidy@tucsonaz.gov City of Tucson Site Zoning and Planning Reviewer Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services |
||
| 04/08/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |