Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0424-02571
Parcel: 119040430

Address:
3646 S 8TH AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0424-02571
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/28/2024 Site Zoning APPROVED
05/29/2024 Site Engineering NOT REQUIRED
05/29/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/14/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0424-02571 (3646 S 8TH AV TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Provide Special Inspection Certificate for Pier Foundation and Concrete installation, with parts A and B completed, IBC 1703, 1704. See structural calculations, Attachment, page 4 of 6 Foundation Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf

2. Provide a Grounding Electrode System at the detached structure per NEC 690.47.
3. Provide complete grounding details for the PV modules, mounting equipment and support structure, NEC 690.41-50.
4. Note on the plans that all underground electrical shall comply with E3803 for minimum burial depths.

5. Where live parts of electrical equipment are operating at 50 to 1000 volts, such equipment shall be guarded against accidental contact by approved enclosures or other approved means, NEC110.27(A).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
04/29/2024 PDSD Application Completeness Express REVIEW COMPLETED