Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0424-02530
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/29/2024 | Site Engineering | NOT REQUIRED | |||
| 05/29/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/14/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0424-02530 (6822 S 4TH AV TUCSON, AZ 85756) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. Please include the existing solar system in the electrical line diagrams and wire schedule calculations. This is required for verification of interconnection and conductor and OCPD sizing compliance. 690.8, 705.12. 2. The #10 awg CU conductor, from the Dedicated Load Center to the (E) Sub Panel, is undersized for the given 40A OCPD. OCPD for copper conductor may not exceed 30A for #10 rating required by NEC 240.4(D)(small conductors). Show conductors sized per NEC 310.15(B)(16). Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 04/29/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |