Permit Number: TC-RES-0424-02431
Parcel: 136381940

Address:
7221 E ROSE DR

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.3

Permit Number - TC-RES-0424-02431
Review Name: RESIDENTIAL NEW DWELLING v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/16/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/16/2025 Residential Zoning PENDING ASSIGNMENT
12/16/2025 Residential Building REQUIRES RESUBMIT TC-RES-0424-02431 2nd
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. The plans require sufficient detail for demonstrating an awareness of minimum building code compliance for passing all progress inspections.

Provide a response letter on separate file with submitting the updated construction plan set.

Consider using a design professional if unfamiliar with construction documentation.

Provide one construction plan set file with a site plan and sheets 1.2 and 2.2 in a single file.

Provide a clear and concise construction plan set. The submitted plans are not readable.

Sample plans are available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits

SECTIONS - DETAILS:

1. Clarify detail #1 on 2.2 showing the wall assembly with a 6” clearance above the ground or 2” clearance above an exterior concrete surface, R317.1 item 5. The stucco stop may extend to 4” above the ground. ½” anchor bolts are required.

MECHANICAL PLANS:

1. Show heating/cooling facilities in the proposed rooms, R303.9.

ELECTRICAL PLANS:

1. Show the location of bedroom smoke alarms and note if they exist or proposed, R314.3.

If you have any questions, please contact:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
----------------------
12/15/2025 PDSD Application Completeness Express REVIEW COMPLETED