Review Details: RESIDENTIAL SIMPLE REVIEW v.3
Permit Number - TC-RES-0424-02369
Review Name: RESIDENTIAL SIMPLE REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/25/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/25/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0424-02369 (3530 E HAMPTON ST TUCSON, AZ 85716) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. The ¾” pipe to the new tankless W/H is undersized for the given length and demand. At 40 feet of pipe length and a demand of 180k BTU, 1” pipe is required. 2. Size the pipe based on the length from the meter to the attached appliance and max total Branch demand of all attached appliances using Table G2413.4(1) (Metallic Pipe). Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||