Permit Number: TC-RES-0424-02225
Parcel: 205942260

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.2

Permit Number - TC-RES-0424-02225
Review Name: RESIDENTIAL SOLAR v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2024 Site Engineering NOT REQUIRED
06/27/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
06/11/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0424-02225 (9494 S DESERT FAUNA LP TUCSON, AZ 85747)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Update the electrical load calculations which demonstrate that the premises electrical system has load capacity to accommodate the EV charging load, Include the EV charger in the load calculations as a continuous use item. See 2018 IRC E3704.2.
2. Include the EV charger in the line diagram and show the EV OCPD in the updated Main Panel Schedule.
3. Show the location of the EV charger on the site plan.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
05/29/2024 PDSD Application Completeness REVIEW COMPLETED