Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0424-02169
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/11/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/11/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0424-02169 (2820 N BARRIO MESQUITE PL TUCSON, AZ 85712) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). 1. Size the pipe based on the length from the meter to the farthest attached appliance on the branch and max total Branch demand of all attached appliances on the branch using Table G2413.4(1) (Metallic Pipe), Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1. 2. The ½” pipe to the new water heater is undersized for the 180,000 BTUh demand and total length of 43 feet to the water heater. Minimum size required for this segment is 1”. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 04/11/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |