Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.2
Permit Number - TC-RES-0424-02087
Review Name: RESIDENTIAL SOLAR v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/29/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/29/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0424-02087 (1705 W COCHRAN ST TUCSON, AZ 85746) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. The Engineer’s seal for structural did not transfer correctly to the plans. Please reupload with the seal correctly applied. Also, provide an updated structural calculation letter for the updated location of the PV modules. 2. The #10 awg CU conductor, from the Dedicated Load Center to the Main Panel, is undersized for the given 35A OCPD. OCPD for copper conductor may not exceed 30A for #10 rating required by NEC 240.4(D)(small conductors). Show conductors sized per NEC 310.15(B)(16). Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 05/24/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |