Permit Number: TC-RES-0424-02036
Parcel: 138080190

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-0424-02036
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/12/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/12/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0424-02036 (757 W CALLE ANTONIA TUCSON, AZ 85706)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

Water line review:
1. Note and specify all piping materials and sizes, P2609.
2. Non-metallic water line requires a blue tracer line.
3. Minimum burial depth, 12”, P2603.5.

Gas line review:
1. Size the pipe based on the length from the meter to the farthest attached appliance on the branch and max total Branch demand of all attached appliances on the branch using Table G2413.4(1) (Metallic Pipe), Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1.
2. The addition of a new tankless water heater requires that the existing system be enlarged to meet the total demand, or a new dedicated line is required for the tankless water heater, G2412.3, G2412.4.
3. For the given lengths and demands, the main 1” gas line is undersized as is the ¾” gas line. Provide sizes in compliance with G2413.4.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
04/12/2024 PDSD Application Completeness Express REVIEW COMPLETED