Permit Number: TC-RES-0424-01918
Parcel: 119041920

Address:
3556 S CLARK AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0424-01918
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2024 Fire New Construction NOT REQUIRED
05/03/2024 Site Engineering NOT REQUIRED
05/07/2024 Site Landscape NOT REQUIRED
05/07/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/18/2024 Residential Building REQUIRES RESUBMIT TC-RES-0424-01918
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. The plans require sufficient detail for demonstrating an awareness of minimum building code compliance for passing all progress inspections.

Consider using a design professional if unfamiliar with construction documentation.

The construction plan set should show all proposed additions, repairs and alterations to the building and parcel.

Separate the submitted files with construction plans and support documents in different files.

Provide a clear and concise construction plan set. Sample plans are available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits

SITE PLAN:

Provide a site plan showing utilities for the dwelling, R106.1.1. Show the location of all utility lines from property line to building(s) along with required alterations.

FLOOR PLAN:

Provide a floor plan showing each proposed room with labeled function and dimensions. Show door locations and window sizes with type identified as XO or SH. Altered bedrooms require code compliance for egress, R310.

STRUCTURAL PLANS:

1. Provide a complete plan set showing materials and fastener sizes with 2018 IRC prescriptive compliance or provide an Arizona professional stamped plan set showing performance compliance with wind loading conditions, R301.1.

SECTIONS - DETAILS:

1. Provide a complete cross-section detail showing proposed material sizes and ratings, R106.1.
2. Provide a structure section showing existing and proposed features including a foundation, framing, sills, anchoring, sheathing and insulation, R106.1.
3. Provide a complete cross-section detail showing type and size of framing, exterior wood siding, insulation, interior sheathing, and pressure treated sill anchored with ½” x 10” bolts. Show the wall assembly with a 6” clearance above the ground or 2” clearance above an exterior concrete surface, R317.1 item 5.
4. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF.
5. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. Attic space outside of the thermal barrier requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2 or an unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.

MECHANICAL PLANS:

1. Show any proposed changes, R301.1.

ELECTRICAL PLANS:

1. Designate the circuit number at the location of each light fixture, receptacle, appliance, and equipment disconnect switch, E3404.12.
2. Show a smoke alarm in each bedroom and outside the doorway in the immediate vicinity, R314.3.
3. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2.
4. Notate interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.16.

INTERNATIONAL ENERGY CONSERVATION CODE:

Provide insulation details minimum (R-13 walls and R-30 small additions or otherwise R-38 ceiling) showing code compliant placement of materials and ratings, N1101. Windows require a solar heat gain of 0.25 or better.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
05/01/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-RES-0424-01918
3556 S CLARK AV . – R-2
Bedroom Enlargements (1st Review)

TRANSMITTAL DATE: May 1, 2024

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10.

1. Based on aerial photos there has been some type of addition to the southwest corner of the residence. These additions appear sometime after 2021. There is also some type of shade structure located near the northwest corner of the property that shows up after 2020. Zoning was not able to find approved permit documents for these additions. Either provide approved permit documents or include this addition within this permit.

2. Provide a residential plot plan that meets the requirements fount at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Plan-Examples/Plot-Plan-Example, with the next submittal.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
04/03/2024 PDSD Application Completeness Express REVIEW COMPLETED