Permit Number: TC-RES-0423-04752
Parcel: 125073440

Address:
2204 E 6TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.2

Permit Number - TC-RES-0423-04752
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/27/2023 Residential Building REQUIRES RESUBMIT Permit Review 2nd Submittal: TC-RES-0423-04752 (2204 E 6TH ST TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken.
Code reference, 2018 International Residential Code (IRC).

Gas connection to the new tankless water heater was not addressed.
1. Modification of the gas appliances requires a gas piping plan, G2413.4.1, Table G2413.4(1). https://www.tucsonaz.gov/files/pdsd/permits/GAS_HANDOUT_2018_IRC_2019.2.4.pdf

2. Provide gas piping plan. Show connection, lengths and sizes, from gas meter to all gas appliances. See https://www.tucsonaz.gov/files/pdsd/permits/GAS_HANDOUT_2018_IRC_2019.2.4.pdf
https://www.tucsonaz.gov/files/pdsd/permits/Gas_Piping_Template.pdf
https://www.tucsonaz.gov/files/pdsd/permits/Sample_Gas_Template_0.pdf
3. Provide manufacturer’s spec sheet for tankless water heater demonstrating appliance fuel input, venting requirements and shielding from contact requirements. G2408.1 General, G2406.3 Outdoor locations, M1306.1 & G2408.5 Clearances to combustible construction.
4. Provide total demand from all appliances.
5. Provide length from meter to all appliances. G2413.4.1 Longest length method: Length is from Meter to the furthest connected appliance. Use this same length to determine all pipe sizes.
6. Use Table G2413.4(1) (Metallic Pipe) to calculate correct required pipe sizes.
7. Protect from accidental contact, M2005.1.
8. Show venting meets clearance requirements from opening windows and doors, other air intake points, and pedestrian walkways, G2427.8. Provide consistent placement of the tankless water heater in the plans, Sheets A-1 & MP-1 show different locations.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
06/06/2023 PDSD Application Completeness Express REVIEW COMPLETED