Permit Number: TC-RES-0423-04726
Parcel: 130083640

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.3

Permit Number - TC-RES-0423-04726
Review Name: RESIDENTIAL NEW DWELLING v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2024 Site Engineering NOT REQUIRED
03/26/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/11/2024 Residential Building REQUIRES RESUBMIT Permit Review TC-RES-0423-04726 (3538 E SYLVANE ST TUCSON, AZ 85713)
2nd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

Code reference, 2018 International Residential Code (IRC).

Bedroom:
1. Provide and show a code compliant emergency escape and rescue opening for BEDOOM 4, R310.1. The 3040XO window does not meet the minimum requirements in R310.2.1. The net clear width shall not be less than 20”.
2. Show a roof ventilation plan with a minimum 1” air space between the insulation and roof sheathing, R806. And show attic vent openings effectively sized for the attic area per R806.2. Attic space requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2

Laundry area:
3. Show one 20 AMP branch circuit in the laundry area; this circuit may not serve other locations, E3703.3 and 3901.8. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description, and showing the dedicated laundry circuit, E3404.13 & E3706.2.
4. Clothes Washer GFCI: receptacles require readily accessible protection typically from an upstream device, E3902.9 & 10. Add notation to plans.
5. Show dryer vent size and location for venting to exterior, M1501.
6. Show all drainage fixtures with connection to the public sewer system, P2602.1. The clothes washer requires connection to the building drain system.
7. Show horizontal branch drainpipes sized with acceptable number of fixture units, Table P3005.4.1. (max 6 units on 2” pipe size)


Main bathroom:
8. Show bathroom (without a window) exhaust fan locations with minimum 50 CFM rating and duct to the exterior, R303.3 and M1505.


Proposed Porch Review:

9. The roof structure may not extend to a point closer than 3 feet from the neighboring property line without fire rated protection for fire spread. Provide compliance with R302.1 (City of Tucson Amended) by removing the roof placed within 3 feet to the property line or provide a complete wall barrier with not less than one-hour fire-resistive construction in compliance with IBC Table 721.1(2). This construction or separation is required from ground to roof and from end to end of the roof which resists fire spread across the property line.
10. Provide framing details to show attachment of new roof structures to existing structure. https://www.tucsonaz.gov/files/pdsd/pdfs/Porch_Sample.pdf. The detail on sheet A 4, wall section 1, is not consistent with the elevation views and roof slope. This porch attachment requires either a code compliant ledger or show the rafters resting on the existing wall.
11. Specify all ledgers connected to masonry walls with 3x material, Figure R606.11 (1).
12. The 6x8 beam is undersized for the given span and tributary area. Show a beam sized for the given conditions.
13. Clarify the roof sheathing being used for the new porch. Show a minimum structural sheathing thickness of 5/8” for T1-11 on roof, R802.1.
14. Show structural roof sheathing with fastening to (2x) structural framing members in compliance with Table R602.3 (1), item 30 and 31.
15. See the Porch sample page 3 for examples of compliant porch attachments. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/porch_sample.pdf
16. Sheet A2.0 shows the proposed porch extending beyond the existing wall. There is no support structure shown for this portion of the porch. What is holding up the porch roof structure when extends beyond the existing support wall?

17. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. NOTE: Full cutoff fixtures rated at 35,000 Kelvin and under a canopy are exempt, ODLC 401.2.1(3).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
03/26/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-RES-0423-04726
3538 E SYLVANE ST. – R-2
Extend Porch (1st Review)

TRANSMITTAL DATE: March 26, 2024

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10.

1. The lot dimensions are not correct. Review the Citation Park final plat found at https://onbase.pima.gov/publicaccess/DS_NextGen_Single/etc/cq/results.html?cqid=240&OBKey__552_1=15033, and provide the correct lot dimensions.

2. Adjacent to “ACREAGE OF LOT” you list “9114” which appears to be the lot square footage but adjacent to “LOT” you list “6.956.4 SQ. FT. but based on the dimensions show on the Citation Park final plat the lot size should be 6,384 sq. ft.

3. The lot coverage calculation is not correct. Review UDC Article 6.4.3 and the example shown on the Residential Plot Plan Requirements found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Plan-Examples/Plot-Plan-Example, and provide a correct lot coverage calculation. Per UDC Article 6.4.3.C.1.a Roofed areas, porches, open on at least one side are not included in the calculation.

4. Based on a height of 7’-8” the required perimeter yard setback from the proposed porch addition to the west property line is 6’-0”. As a setback dimension was not provided from the porch addition to the west property line Zoning cannot provide the required comments to process a Design Development Option (DDO).

DDO application and requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. If you have questions about the DDO application or process please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or Georgia Pennington at Georgia.Pennington@tucsonaz.gov.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
02/25/2024 PDSD Application Completeness Express REVIEW COMPLETED