Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/23/2023 Residential Building REQUIRES RESUBMIT Permit Review TC-RES-0423-04707 (5901 E JUAREZ ST TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken.
Code reference, 2018 International Residential Code (IRC).

General Notes:
1. Clarify the intended use of this new bedroom. If this bedroom addition is for an additional room for the assisted living facility this residential permit will need to be withdrawn and commercial plans submitted for the assisted living facility. The plans will need to be stamped by a licensed architect.
Site Plan/Floor Plan:
2. Street view shows there is an existing window within the carport that will be closed in with this addition. I could not see another window on the East side wall for the existing bedroom. Provide a picture of the East side wall showing the existence of a code compliant emergency egress/access window for the existing bedroom. Show compliance with R310 providing egress from bedrooms with minimum net clear opening area of 5 SQ FT. Also, show the minimum net clear opening dimension of 24” height and 20” width, and maximum sill height of 44”.
Electrical plans:
3. Provide a panel schedule showing the OCPD and wire size of the branch circuit being used for the new bedroom, E3602.1 & E3706.2.
4. Show that the number of receptacle outlets on the branch circuit are within the overcurrent protection rating, E3702.2. 20A circuits may serve an area not greater than 800 SF. 15A circuits may serve an area not greater than 600 SF, E3704.4.
5. Designate the circuit number at the location of each light fixture, receptacle, appliance, and equipment disconnect switch, E3404.12.
Section/Details:
6. Attic space requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2 or an unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
05/12/2023 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-RES-0423-04707
5901 E. Juarez St. – R-1
Convert Carport to Bedroom (1st Review)

TRANSMITTAL DATE: May 12, 2023

This comment was not addressed. Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

1. The lot coverage does not appear to be correct. Per UDC Article 6.4.3.B.3.b vehicle use area whether improved or unimproved, is included in the lot coverage.

2. Based on the submitted plans this single-family residence now will have 6 bedrooms. Clearly demonstrate on the plan how the requirements of UDC Article 4.9.7.B.7 “For any new single-family dwelling in the R-1 zone with five bedrooms, three parking spaces are required. For every bedroom over five, one additional space is required for each bedroom. For all single-family dwellings in the R-1 zone with five or more bedrooms, and for all lots containing two or more single-family dwellings, with the second dwelling having more than one bedroom, all parking spaces must be located on-site, either in a side or rear perimeter yard. Parking spaces may not be located in a vehicular use area in any front street perimeter yard. A parking area is not required to be developed to a commercial standard. A dustproof parking surface is required to at least a minimum of two inches of compacted pea gravel. An existing covered residential parking area may be used” are met.

3. Zoning acknowledges that prior permits have been approved for an assisted living facility at this site. If this bedroom addition is for an additional room for the assisted living facility this residential permit will need to be withdrawn and commercial plans submitted for the assisted living facility. The plans will need to be stamped by a licensed architect.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov
05/01/2023 PDSD Application Completeness Express REVIEW COMPLETED
05/04/2023 Site Engineering REVIEW COMPLETED