Permit Number: TC-RES-0423-04657
Parcel: 13320127A

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0423-04657
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/19/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0423-04657 (6311 E BRIAN KENT TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC)

1. Building cannot approve without Zoning approval for an accessory structure on an adjoining parcel.
2. Provide Pima County registered easement documentation for all solar placements and electrical runs.
3. Where PV source and output circuits operating at maximum system voltages greater than 30 volts are installed in readily accessible locations, circuit conductors shall be guarded or installed in Type MC Cable or in a raceway, NEC 690.31(A).
4. Where live parts of electrical equipment are operating at 50 to 1000 volts, such equipment shall be guarded against accidental contact by approved enclosures or other approved means, NEC110.27(A).
5. Where subject to physical damage, conductors, raceways, equipment, and cables shall be protected. NEC 300.4 Protection Against Physical Damage, NEC110.27(B) Prevent Physical Damage.
6. Show electrical burial in compliance with NEC Table 300.5.
Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
05/23/2023 Site Zoning REQUIRES RESUBMIT FROM: Iman Monshizadeh
PDSD Zoning Review Section
PROJECT: TC-RES-0423-04657 / Solar addition
Plot Plan Review (1st Review)
6311 E BRIAN KENT / R-1 Zone
TRANSMITTAL DATE: 05/23/2023

1. Per zoning administration and residential building review, PV system cannot provide power to structures that are not within the subject parcel. Zoning cannot approve until either:
a. The parcels are combined.
b. The PV array is moved to the same parcel as the primary residence (6311 E BRIAN KENT)
2. Structures located in the front perimeter yard of a parcel have a maximum square footage of 400sf. If PV array is moved it cannot be located within the width between the building and the front perimeter yard unless it is smaller or equal to 400sf in size.


Resubmittal instructions: https://www.tucsonaz.gov/files/pdsd/pdfs/Resubmittals.pdf

For questions regarding Zoning comments, please contact me at: Iman.Monshizadeh@tucsonaz.gov
04/27/2023 PDSD Application Completeness Express REVIEW COMPLETED