Permit Number: TC-RES-0423-04631
Parcel: 13332437A

Address:
9221 E 6TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-RES-0423-04631
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
04/28/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Please provide total load of house for review and we need the total length to the farthest appliance. Refence G2413.4.1
G2415.17.3 (404.17.3) Tracer.
A yellow insulated copper tracer wire or other approved conductor, or a product specifically designed for that purpose, shall be installed adjacent to underground nonmetallic piping. Access shall be provided to the tracer wire or the tracer wire shall terminate above ground at each end of the nonmetallic piping. The tracer wire size shall be not less than 18 AWG and the insulation type shall be suitable for direct burial.
04/21/2023 PDSD Application Completeness REVIEW COMPLETED