06/06/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/06/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0423-04474 (5343 S WEDGEWOOD PL TUCSON, AZ 85746)
Submittal 2
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken.
Code reference, 2018 International Residential Code (IRC).

1. Page PV 3, #8 wire is undersized for the combined current. NEC 690.8(B).
2. Show correct wire size for combined current from the 125A Enphase combiner panel to the main service panel. The minimum size required for the given current is 6 awg CO.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
05/24/2023 PDSD Application Completeness Express REVIEW COMPLETED