Permit Number: TC-RES-0423-04425
Parcel: 11714383G

Address:
746 S OSBORNE AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.5

Permit Number - TC-RES-0423-04425
Review Name: RESIDENTIAL NEW DWELLING v.5
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/22/2026 Historic REQUIRES RESUBMIT This project has been reviewed separately as new build and garage and Pool House Rehabilitation since 2025
BHHZAB-7/14/2025
Recommended approval of the plan as presented with the conditions of (1) Match the architectural features at the pool house with the new house build and(2) Eliminate the fire rated extended wall on the north side of the pool house.
On 8/28/2025:
PRS recommended approval of the Second unit and garage as presented, with the following conditions:
a. The north 3'-6" setback is acceptable
b. Windows and doors are to be clarified on the plans to be metal-clad wood
c. Awnings to be clarified on the plans to be corrugated metal and wood
d. The applicant is to update the plans as needed to reflect the final decision, including removal of the transoms
On 8/28/2025, recommended to continue the Pool House rehabilitation with the following conditions:
1. The applicant is to work with an adobe specialist and an experienced structural engineer to come up with a preservation plan for rehabilitation and reuse that maintains the integrity and contributing status of the adobe structure
2. The adobe structure proposed as a bathhouse/casita portion of the project is not approved, and PRS would like to see this portion come back for review
On 3/26/2026
PRS recommended approval of the pool house with conditions:
1. The applicant is to provide a design solution for the drainage at the north elevation to be reviewed and approved by the historic preservation office.
2. Update the elevations in the drawing set to notate the correct materials.

Next steps: Applicant to resubmit a revised package the shows ALL conditions of the BHHZAB 7/14/2025 and PRS 8/28/2025 and 3/26/2026. All these conditions MUST be shown on plans by key note#, plan sheet # or clouding etc. Revised should be in a single compressed pdf file.
Questions: Contact Michael.Taku@tucsonaz.gov
06/04/2026 Residential Building REQUIRES RESUBMIT TC-RES-0423-04425 3rd
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:

This permit description is now for a carriage house alteration to pool room as shown on the last submitted plans, R106.1.

The construction of an ADU will require a separate application and plan set with 2024 IRC compliance. A permit requires the correct application type. An ADU requires a new dwelling permit application. This activity TC-RES-0423-04425 is an alteration permit type.

Submit response letter addressing the comments when resubmitting an updated plan set for the pool room.

SITE PLAN:

1. Note the ADU for future construction on separate permit.
2. Show a sewer line connection from the pool room to an existing sewer line, R106.1.1

PLANS:

1. Portions of a building placed within the fire separation distance to an adjoining property line require separation with a 1-hour fire-resistance rated assembly without openings, R302.3. Provide a detail or update keynote #9, sheet 3, showing compliance with 703.3 of the 2018 IBC.
2. A roof projection may not extend closer than 24” to the adjoining (neighboring) property line. Any part of a roof projection extending into the 3-foot fire separation distance from the property line requires not less than one-hour fire-resistive construction on the underside, R302.1 (City of Tucson Amended). Update the north roof overhang on sheet 9.

SECTIONS - DETAILS:

1. Remove the ventilation calculation from sheet 6, R806.2.
2. An unvented roof assembly requires both a minimum R-5 rigid foam board and batt insulation for a total R-30 for the building under 500 SF, R806.5. Update the non-attic note on sheet 6 with a consistent design with detail #17 & 18 on sheet 7.

MECHANICAL PLANS:

1. Show the HVAC system size for the building demand in accordance with M1401.3, M1601.1. A 1-ton unit (keynote #1) is oversized.

ELECTRICAL PLANS:

1. Update the Riser Diagram for showing the pool house sub panel which requires feeder (breaker) protection on the main panel, NEC 225.30 and E3403.
2. Show the ADU panel on a separate permit, NEC 225.30 and E3403.
3. Remove the exterior receptacle on circuit #45/47 from the plan, R106.1.1.
4. Remove circuit #16 from the panel schedule, R106.1.1
5. Show the receptacle on circuit #14 within 3’ of the sink, E3901.6.
6. Show the bathroom receptacle on circuit #9 with GFCI protection, E3902. May be placed on circuit #14.

If you have any questions, please contact:
Kenneth.VanKarsen@tucsonaz.gov
City of Tucson Residential Building Safety
06/12/2026 Residential Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL
FROM: Roxanne Johnston
Planner
PROJECT: TC-RES-0423-04425
746 S Osbourne Av Tucson, AZ 85701
Plan Review (5th Review)

TRANSMITTAL DATE: 06/12/2026

This building site is located within the HO-3 zones (Unified Development Code (UDC) Articles 4.8-4 and 4.7.15). An accessory dwelling unit is a permitted use in these zones, subject to Use Specific Standards 6.6.3.
RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Please correct plans, as noted in the comments below, along with a Response Letter indicating how all Site Zoning comments were addressed.

1. Records show that the process for SD-0225-0018 (Historic Review) has not been completed. The information requested by Michael Taku in his review completed on 2/24/26 indicates that the materials were to be uploaded to the Historic file under SD-0225-0018 and not the Building permit file. Without Historic Preservation approval, zoning will not be able to approve TC-RES-0423-04425. Please upload the decision letter for the Historic Review and the Response Letter addressing all comments with the next submittal materials.

2. If you need clarification or have questions regarding the Historic Review process please contact Michael Taku at Michael.Taku@tucsonaz.gov

3. Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted for the next review.

For questions regarding Zoning comments, please contact me at: Roxanne.Johnston@tucsonaz.gov.
06/03/2026 PDSD Application Completeness Express REVIEW COMPLETED