Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-RES-0423-04379
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/13/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/13/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0423-04379 (4149 E HOLMES ST TUCSON, AZ 85711) Plan review for the above referenced permit has been completed. This letter reflects comments to be addressed. All code references are to the 2018 International Residential Code. Provide updated plans and calculations with a written response to each of the notated items indicating action taken. 1. Show locations and scope of repair work being done. 2. Line from Meter to T at the first furnace (60k btu) is undersized. 1 ¼” required. 3. Line from T at the first furnace to the second furnace T requires 1” for the entire length. 4. Final Segment to the second furnace (100k btu) requires ¾”. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 04/13/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |