Permit Number: TC-RES-0423-04253
Parcel: 125080490

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0423-04253
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/17/2023 Site Landscape NOT REQUIRED
05/08/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/08/2023 Residential Building REQUIRES RESUBMIT TC-RES-0423-04253
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

Clarify the original structure usage. Provide the permit number with a final inspection.

An independent dwelling (ADU) requires utility (electrical & water) separation so that one dwelling is not dependent upon another for water or electrical service.

Each dwelling unit with kitchen requires a separate Pima County assigned street address after Zoning approval, R319.

An impact fee payment is required for an ADU at the time of permit payment.

SITE PLAN:

1. Show the location and size of buildings, utility meters and gas, water, electric and sewer lines from property line to each building, R106.1.1. Each dwelling requires an independent electrical service and water supply shut off devices. Identify the utility lines requiring upgrade or replacement.
2. Show a street address for each dwelling on the site plan, R319.

PLANS:

1. Provide a complete construction plan set showing 2018 IRC compliance, R106.1.

SECTIONS - DETAILS:

1. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation or need for providing air-impermeable rigid insulation at the roof, R806.

PLUMBING PLANS:

1. Tucson Water Department limits flow rates for each water meter size in compliance with P2903.7. Show an appropriate yard pipe for supporting the existing and proposed dwellings and show an appropriate water meter size.
2. Show an individual accessible water supply shut off for the proposed dwelling unit, P2903.9.1.
3. Show gas, water, drain, and vent sizes, R106.1.
4. Show each gas pipe segment sized in conformance with Table G2413.4(1). Existing gas pipes may require upgrading with this system alteration.

MECHANICAL PLANS:

1. Show the HVAC system size for the building demand in accordance with M1401.3, M1601.1.

ELECTRICAL PLANS:

1. Show a Riser Diagram with a service disconnect for each dwelling without service disruption of the other dwelling, NEC 225.30 and E3403.
2. Show the location of GFCI receptacles and smoke alarms, R314.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
(520) 837-4912 PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/pdsd
05/02/2023 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-RES-0423-04253
215 N Tucson Bl. – R-1
Convert Garage to Dwelling Unit (1st Review)

TRANSMITTAL DATE: May 2, 2023

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf. The plot plan shall include but not limited to:
a. The plot plan shall be drawn at an engineering scale, i.e. 1” = 10’, 1” = 20’.
b. Provide a lot coverage calculation on the plan
c. Provide the legal description, “COUNTRY CLUB HOMESITES LOT 11 BLK 1” on the plot plan.
d. The parcel shown on the plan does match the final plat in size or shape.

2. The As-Built configuration shown on the plan constitutes a second dwelling unit. Per UDC TABLE 4.8-2: PERMITTED USES - URBAN RESIDENTIAL ZONES, R-1 ZONE, a parcel in the r-1 zone is required to be 10,000 square feet to allow two (2) dwelling units. Per TABLE 4.8-2: PERMITTED USES - URBAN RESIDENTIAL ZONES, R-1 ZONE an Accessory Dwelling Unit (ADU) is allowed but per UDC Article 6.6.3.B.5 For lots less than 6,500 square feet in size, the accessory dwelling unit is limited to 650 square feet of gross floor area. For lots equal to or greater than 6,500 square feet, the accessory dwelling unit is limited to 10% of the lot size, not to exceed 1,000 square feet of gross floor area. Based on the Country Club Homesites final plat the dimensions of this parcel are 120.22 x 53.5 for a total square footage of 6,432 sq. ft. Based on a lot size of 6,432 and ADU would be limited to 650 sq. ft. At a minimum a Board of Adjustment for Variance will be required to permit the proposed conversion as shown on the plan. A rezoning maybe required. Contact Mark Castro at Mark.Castro@tucsonaz.gov to determine what process will be required. The other option is to remove the kitchen from the plan and convert the structure back to the garage with a sleeping quarters, Bedroom.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov
04/13/2023 Fire New Construction REVIEW COMPLETED
04/10/2023 PDSD Application Completeness Express REVIEW COMPLETED
04/20/2023 Site Engineering REVIEW COMPLETED