Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-RES-0423-04227
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2023 PDSD Application Completeness Express REQUIRES RESUBMIT Resubmit with a complete gas piping template. If you are replacing or adding gas piping, a plan is required. It is important to verify that the pipe, being replaced or added to, is the correct size for the current code. Existing gas piping may not be properly sized for the currently adopted code. In order to perform a complete plan review, the following items must be specified:
 The total length of the pipe measured from the meter to the furthest appliance
 The Btu/h input all gas-fired appliances supplied by the gas meter
 Future connections or capped “tee” outlets must be included on your plan because the system must be sized to handle any future demand