Permit Number: TC-RES-0423-04087
Parcel: 110111660

Address:
4934 E COPPER ST

Review Status: Requires Resubmit

Review Details: RESTAMP - RESIDENTIAL v.1

Permit Number - TC-RES-0423-04087
Review Name: RESTAMP - RESIDENTIAL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2023 Site Landscape NOT REQUIRED
07/07/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/07/2023 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-RES-0423-04087
4934 E. Copper St. - R-1
Attached Sleeping Quarters (1st Review)

TRANSMITTAL DATE: July 7, 2023

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9.

1. The proposed attached sleeping quarters does not qualify as a sleeping quarters and impact will apply if the sleep quarter remains as shown. If you wish for the sleeping quarters to qualify as a sleeping quarters the double bowl sink will need to be replaced with a single bowl bar type sink and the refrigerator will need to be an under counter refrigerator. Zoning acknowledges that the refrigerator is labeled “UNDER COUNTER” but it is shown as a full size.

2. The ‘EXT’G CARPORT-3 (PARKING) (TANDEM) shows up on aerial photos sometime after 2016. Zoning was not able to find approved permit documents for this carport. Either provide approved permit documents with the next submittal or include the carport within this permit. As it does not appear that this structure meets perimeter yard setbacks a Design Development may be required once the applicable heights and setback dimensions are provided.

3. The dimension from the center line of Copper to the property line is not correct. Review the final plat and provide the correct dimension.

4. The lot coverage calculation is not correct. Per UDC Article 6.4.3.C.1.a porches open on at least one side are not included.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.