Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR REVISION v.1
Permit Number - TC-RES-0326-01490
Review Name: RESIDENTIAL SOLAR REVISION v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/04/2026 | Residential Zoning | APPROVED | 1. Please be aware that during Site Zoning review of this permit, it was found that unpermitted work may have occurred on this site. Refer to sheet PV-1. Since the solar installation is not proposed to be placed upon or associated with the unpermitted structure(s), this will not prevent Site Zoning approval of this solar installation permit. That said, future work on the site may be delayed until this unpermitted work is addressed. You may submit a separate “Residential Addition/Alteration” or “Residential Fence/Wall” permit to address this work. Approval of this permit is only for the residential solar installation and does not constitute a Site Zoning approval of the entire site. |
||
| 05/04/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/30/2026 | Light Residential Building Review (OIP) - Standard | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comment: 1) Please provide the required permanent field marking in accordance with NEC 705.12(B)(3). The service equipment shall be clearly labeled "WARNING: EQUIPMENT FED BY MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT PROTECTION DEVICE SHALL NOT EXCEED AMPACITY OF BUSBAR." |
||
| 04/28/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |