Permit Review Detail
Review Status: Approved
Review Details: RESIDENTIAL SIMPLE REVIEW v.2
Permit Number - TC-RES-0326-01482
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Approved
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/09/2026 | Light Residential Building Review (OIP) Express | APPROVED | SPD must be installed within or immediately adjacent to the Main Service Panel. SPD must have a nominal discharge current rating not less than 10kA, be UL 1449, and be Type 1 or Type 2. 230.67 | ||
| 04/10/2026 | Bldg Permits - Post Review Express | REVIEW COMPLETED | |||
| 04/09/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |