Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0326-01468
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/24/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/24/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov 1) A Surge Protection Device (SPD) must be identified on the plans. This requirement can be satisfied by providing the manufacturer’s specifications for the SPD to be installed to verify that it is UL listed and code compliant E606.5 NEC 230.67 2) Please clarify if a new dual meter service panel will be installed or if there will be individual service panels to be replaced. More comments may be forthcoming |
||
| 03/24/2026 | PDSD Application Completeness Express | REQUIRES RESUBMIT | If you have questions, please contact Janet Torres at PDSD-Permits@tucsonaz.gov. This permit application will be applied to 3613 S BELMAR AV. For the address of 3615 S BELMAR AV, please apply for a separate permit. When resubmitting for the second address, please ONLY include the address of 3615 S BELMAR AV, not both. |