Permit Number: TC-RES-0326-01423
Parcel: 125042020

Address:
915 N TUCSON BL

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.1

Permit Number - TC-RES-0326-01423
Review Name: RESIDENTIAL ADD/ALT v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2026 Residential Engineering NOT REQUIRED
04/06/2026 Residential Zoning NOT REQUIRED
04/09/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/09/2026 Residential Building - Standard REQUIRES RESUBMIT TC-RES-0326-01423
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2024 International Residential Code and 2018 International Energy Conservation Code. The 2024 International Energy Conservation Code takes effect July 1st. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2024 IRC code compliance. The plans require sufficient detail for demonstrating minimum building code compliance for passing all progress inspections.

Place the 2024 IRC reference code on sheet #1 rather than throughout the plans.

Provide a separate response letter addressing each comment with location of change on the plans.

PLANS:

1. Remove all outdated code references, R106.1.1. Incorrect entries were found on sheets 3, 4 & 5. See red lined plans.

ELECTRICAL PLANS:

1. Show a surge-protective device (SPD) as an integral part of or placed immediately adjacent to the service equipment, E3606.5.
2. Provide GFCI protection for appliance receptacle outlets, E3902.12. Include:
1. Drinking water coolers
2. High pressure spray washing machines
3. Sump pumps
4. Dishwashers
5. Electric ranges
6. Wall-mounted ovens
7. Counter-mounted cooking units
8. Clothes dryers
9. Microwave ovens
3. Provide GFCI protection for receptacle outlets and HVAC equipment after September 1, 2026. E3902.14.

If you have any questions, please contact:
Kenneth.VanKarsen@tucsonaz.gov
City of Tucson Residential Building Safety
03/23/2026 PDSD Application Completeness Express REVIEW COMPLETED