Permit Number: TC-RES-0326-01385
Parcel: 110054190

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.1

Permit Number - TC-RES-0326-01385
Review Name: RESIDENTIAL ADD/ALT v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2026 Residential Zoning APPROVED
03/19/2026 Residential Engineering NOT REQUIRED
04/08/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/08/2026 Residential Building - Standard REQUIRES RESUBMIT TC-RES-0326-01385
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2024 International Residential Code and 2018 International Energy Conservation Code. The 2024 International Energy Conservation Code takes effect July 1st. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2024 IRC code compliance.

Provide a separate response letter addressing each comment with location of change on the plans.

PLUMBING PLANS:

1. Show each gas pipe segment sized in conformance with Table G2413.4(1). The existing 1“ gas pipe requires upgrading with this system alteration for 220 CFM @ 135 developed length.

ELECTRICAL PLANS:

1. Clarify the island design (one or two worksurface levels) for evaluating the receptacle locations. Remove receptacles from the exterior face of island and peninsular cabinets where below the countertop. Either provide a vertical assembly listed for countertop (work surface) mounting, or a raceway terminated within the cabinet for future assembly installation, E3901.4.

If you have any questions, please contact:
Kenneth.VanKarsen@tucsonaz.gov
City of Tucson Residential Building Safety
03/19/2026 PDSD Application Completeness Express REVIEW COMPLETED