Permit Number: TC-RES-0326-01375
Parcel: 134240310

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADU v.1

Permit Number - TC-RES-0326-01375
Review Name: RESIDENTIAL ADU v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/06/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/25/2026 Residential Building REQUIRES RESUBMIT TC-RES-0326-01375
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2024 International Residential Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2024 IRC with amendments and building ordinances for all dwellings.

Clarify if the proposal is for a detached addition (without kitchen) or a new dwelling with kitchen. A living unit with kitchen is considered a dwelling (ADU) and will require an impact fee payment when the plans are approved.

A permit requires the correct application type. Request the cancellation of this application for a new dwelling and apply for an addition/alteration permit. These plans do not include a cooking appliance such as a stove, but the application is for an ADU. The addition/alteration permit will become a great cost savings because a dwelling permit requires features not necessary for the space without the cooking appliance.

Provide a separate response letter addressing each comment with location of change on the plans. Submit the letter with the new addition/addition application after submitting a cancellation of this ADU permit.

SITE PLAN:

Show an appropriate water supply pipe size for the parcel fixture units, P2903.6. Either show the proposed ¾” yard pipe connecting directly to the meter or show a 1” supply pipe between the connection point and the meter.

PLANS:

1. Provide manufacturer’s calculations and data for pre-engineered trusses dated and wet-sealed by an engineer who is registered in Arizona, or notate the requirement for deferred submittal, R106.1.
2. Provide a minimum 6 mil polyethylene vapor retarder with joints lapped not less than 6 inches between the concrete floor slab and the base course or the prepared subgrade where a base course does not exist, R506.3.3.
3. Update the code reference at the foundation plan note #3.


SECTIONS - DETAILS:

1. Attic space outside of the thermal barrier requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2. Show a roof design complying with the condensation control requirement.

MECHANICAL PLANS:

1. Show the HVAC system size for the building demand in accordance with M1401.3, M1601.1. A total of 4-tons of cooling is oversized for the building size.
2. Provide demand calculations in accordance with Manual J standards, M1401.3, M1601.1.
3. Identify the device model number providing an adjustable setting and note the minimum continuous setting for providing whole-house mechanical ventilation, R303.4; N1103.6 & M1505.4. A two or three-bedroom dwelling under 1501 SF requires a 45 CFM continuous setting.

ELECTRICAL PLANS:

1. Update the electrical load calculation for determining the total demand and minimum panel feeder size, E3602.2. Apply a 40% factor for loads over 10,000 watts (8,160) and add this amount to the first 10,000 (sub total 13,264) plus the cooling divided by 240 equals 74 Amps.
2. Show a surge-protective device (SPD) as an integral part of or placed immediately adjacent to the service equipment, E3606.5.
3. Show the water heater circuit on the panel schedule, E3702.11
4. Provide GFCI protection for appliance receptacle outlets, E3902.12. Include the washer/dryer.
5. Provide GFCI protection for receptacle outlets and HVAC equipment after September 1, 2026. E3902.14.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

If you have any questions, please contact:
Kenneth.VanKarsen@tucsonaz.gov
City of Tucson Residential Building Safety
03/24/2026 Residential Engineering REQUIRES RESUBMIT Permit: TC-RES-0326-01375
Location: 6306 E FORDHAM DR
Review Date: 3/24/2026
Site Engineering Comments:
1. This site resides within FEMA Zone XS100 and will require the submission and approval of a floodplain use (FPU) permit with elevation certificate. The FPU permit is a separate permit that can be submitted within the "sub-records" tab of this associated building permit through TDC online.
2. The FPU permit will require an elevation certificate to be completed by a registered land surveyor with intermediate and final submissions.
3. For XS100 the Finished Floor Elevation is required to be 1ft-11inches above grade.
4. Based on the Finished floor elevation and surrounding grade, a grading plan is required. The grading plan is a separate permit called a development package and must be applied for through TDC online.
5. The grading plan shall include drainage patterns and any proposed grading (i.e. spot elevations, cut/fill quantities, area of disturbance, grading profile. top/bottom of slope).
6. Final Residential Engineering approval for permit TC-RES-0326-01375 requires review and approval of associated FPU and DP permit.
7. Per the City of Tucson Inclusive Home Design Ordinance (https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/inclusivehomedesignordinance.pdf, all new dwellings have a requirement to provide an “accessible route from public and common areas, including, but not limited to, a driveway or public street or sidewalk”. Draw, dimension, and label an accessible route from the driveway (or apron), sidewalk, or street to an accessible entrance. Ensure the route meets accessibility standards as articulated in 2017 ICC A117.1 Sections 402-403, including the minimum 4ft-width, slope and composition materials.
If you have any questions or concerns, please contact
Corey Hines
Corey.Hines@TucsonAZ.gov
04/06/2026 Residential Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Roxanne Johnston
Planner

PROJECT: TC-RES-0326-01375
6306 E Fordham Dr., Tucson, AZ 85710
ADU (1st Review)

TRANSMITTAL DATE: 04/06/2026

This site is located within the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 - .9.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Correct plans, as noted in the comments below, along with a response letter indicating how all Site Zoning comments were addressed.

1. Add property zoning (R-1) to the site plan. The following link provides a full site plan example used for submittals: https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/plan-samples/full-site-plan_feb2026.pdf
2. Submit a landscape plan on the revised site plan. City of Tucson’s Ordinance No. 12219 was effective as of January 1, 2026. This ordinance is an amendment to the Unified Development Code (UDC) Article 7, Section 7.6.10 and requires landscaping for all new single family residential, middle housing development, and accessory dwellings. The following link provides the requirements: https://middle-housing-cotgis.hub.arcgis.com/pages/background-1
3. Until Residential Engineering review comments have been fully addressed, Site Zoning are unable to approve the plans.
4. Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted for the next review.

The City of Tucson Unified Development Code may be accessed here: www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code . The City of Tucson Ordinance No. 12219, as amended, may be accessed here: https://tucsonaz.hylandcloud.com/221agendaonline/Documents/ViewDocument/ORDINANCE%2012219.pdf?meetingId=1890&documentType=Agenda&itemId=77068&publishId=189435&isSection=false

If you have any questions about this transmittal, please contact Roxanne Johnston at roxanne.johnston@tucsonaz.gov
03/24/2026 PDSD Application Completeness Express REVIEW COMPLETED