Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL ADD/ALT v.3
Permit Number - TC-RES-0326-01363
Review Name: RESIDENTIAL ADD/ALT v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/05/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/05/2026 | Residential Building - Standard | REQUIRES RESUBMIT | This is a 2024 code change. Keynote #9 noting a receptacle below the countertop is no longer allowed. Remove receptacles from the exterior face of island and peninsular cabinets where below the countertop. Either provide a vertical assembly (pop-up) listed for countertop (work surface) mounting, or a raceway terminated within the cabinet for future assembly installation of an above-counter surface installation, E3901.4. |
||
| 04/30/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |