Review Details: RESIDENTIAL ADD/ALT v.3

Permit Number - TC-RES-0326-01363
Review Name: RESIDENTIAL ADD/ALT v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/05/2026 Residential Building - Standard REQUIRES RESUBMIT This is a 2024 code change. Keynote #9 noting a receptacle below the countertop is no longer allowed.

Remove receptacles from the exterior face of island and peninsular cabinets where below the countertop. Either provide a vertical assembly (pop-up) listed for countertop (work surface) mounting, or a raceway terminated within the cabinet for future assembly installation of an above-counter surface installation, E3901.4.
04/30/2026 PDSD Application Completeness Express REVIEW COMPLETED