Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0326-01341
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/17/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/17/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1) Revise the Load calculations, the VA for fixed appliances is incorrectly calculated. This calculation uses the 2017 NEC, as of Jan. 1, the City of Tucson has adopted the 2024 I-codes and 2023 NEC. Verify that all calculations adhere to the variables present in the new code. 2) Provide Manufacturer Specifications of the EV charger to be used. Include any certifications to ensure that the EV is UL listed E404.14.1 3) Show the location of the EV charger is protected from impact. E304.10 4) EV charger must be GFCI-capable or other means of providing GFCI protection E304.9 5) Verify Man. Installation guide for the use of Neutrals and other equipment to be installed (including CTs) as a part of the EV charging system. |
||
| 03/17/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |