Permit Number: TC-RES-0326-01335
Parcel: 12216275B

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-0326-01335
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/19/2026 Addressing Validation REQUIRES RESUBMIT For questions: PDSD-Permits@tucsonaz.gov

There appears to be two units linked to this address. An address change request must be completed through the sub record of this permit to add correct unit number to this permit. Once that request is submitted, please resubmit documents to reflect the updated address.

Instructions can be found here to request change of address: https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/sub-records.pdf

Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
03/19/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT ACTIVITY NO. TC-RES-0226-00821
ADDRESS/PARCEL: (2515 S KEVIN DR TUCSON, AZ 85748)
Submit your revised reports along with a response letter which states how all Building Review Section comments were addressed. Should you have any questions about these comments, I can be reached at ian.gillaspie@tucsonaz.gov.
COMMENTS:
1. Please refer to the Tucson/Pima County Outdoor lighting code for the following comments: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf
2. For the two southern most fixtures: 401.3.3 Fixtures within 25 feet of residential lot lines. Residential and commercial luminaires shall be full cutoff within 25 feet of adjacent residential property lines, measured perpendicular to the lot line. The fixtures provided are not full cutoff.
3. 401.3.4 Flood and spot lamps. Flood or spot lamps shall be aimed no higher than 45 degrees to the horizontal (half-way between straight down and straight to the side) when the source is visible from any adjacent residential property. It is unclear from the provided documents if the fixtures meet this provision.
4. 401.2.1 Unshielded light fixtures installed under canopies, building overhangs, or roof eaves shall be calculated at 100 percent of the luminaire total light output. Installation under canopies, overhangs or roof eaves shall not provide full cutoff classification of unshielded light fixtures.
5. 401.4 Other than Full Cutoff Lighting. Unshielded fixtures or lighting sources shall not exceed 3,000 lumens per luminaire. The lumens of the light fixtures provided are 4200 which exceeds the allowable limit.
6. Please correct and resubmit.
03/19/2026 PDSD Application Completeness Express REVIEW COMPLETED