Permit Number: TC-RES-0326-01225
Parcel: 116191180

Address:
47 N DAVILA CI

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.1

Permit Number - TC-RES-0326-01225
Review Name: RESIDENTIAL ADD/ALT v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2026 Residential Zoning APPROVED
03/12/2026 Residential Engineering NOT REQUIRED
03/26/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/26/2026 Residential Building - Standard REQUIRES RESUBMIT TC-RES-0326-01225
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2024 International Residential Code and 2018 International Energy Conservation Code. The 2024 International Energy Conservation Code takes effect July 1st. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2024 IRC code compliance.

Provide a separate response letter addressing each comment with location of change on the plans.

PLANS:

1. Remove all outdated code references, R106.1.1. Incorrect entries were found on sheets A0.0 and A3.0. See red lined plans.
2. Provide a minimum 6 mil polyethylene vapor retarder with joints lapped not less than 6 inches between the concrete floor slab and the base course or the prepared subgrade where a base course does not exist, R506.3.3.

SECTIONS - DETAILS:

1. Clarify the type of ceiling/roof insulation without attic ventilation, R806. Keynote A23 on sheet A1.0 is not consistent with detail #6/S2.0.

ELECTRICAL PLANS:

1. Clarify if the service panel is proposed for replacement, E3601.
2. Show a surge-protective device (SPD) as an integral part of or placed immediately adjacent to the service equipment, E3606.5.
3. Provide GFCI protection for appliance receptacle outlets, E3902.12. Include:
1. Drinking water coolers
2. High pressure spray washing machines
3. Sump pumps
4. Dishwashers
5. Electric ranges
6. Wall-mounted ovens
7. Counter-mounted cooking units
8. Clothes dryers
9. Microwave ovens
4. Provide GFCI protection for receptacle outlets and HVAC equipment after September 1, 2026. E3902.14.

If you have any questions, please contact:
Kenneth.VanKarsen@tucsonaz.gov
City of Tucson Residential Building Safety
03/11/2026 PDSD Application Completeness Express REVIEW COMPLETED