Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.4
Permit Number - TC-RES-0326-01191
Review Name: RESIDENTIAL SIMPLE REVIEW v.4
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/20/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/20/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1) Please upload a site plan and include the location of all equipment to be installed. 2) Revise the Load calculations, the VA for fixed appliances is incorrectly calculated. This calculation uses the 2017 NEC, as of Jan. 1, the City of Tucson has adopted the 2024 I-codes and 2023 NEC. Verify that all calculations adhere to the variables present in the current code. 3) As the OCPD is to be sized at 60A, a disconnecting means is required within line of sight. E4101.5 NEC 625.43. Please show the location of this disconnecting means on the site plan. **All construction permitted after Jan. 1 2026 shall comply with the 2024 International Building Codes, the 2023 NEC, and 2025 TEP ESRB requirements including all City of Tucson adopted amendments. See this link for more information. https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Building-Codes ** |
||
| 03/20/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |