Permit Number: TC-RES-0326-01120
Parcel: 13101011B

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0326-01120
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/13/2026 Fire New Construction Standard REQUIRES RESUBMIT Please provide hydrant coverage in accordance with IFC 24, 507.5 and IFC 24, B105.1(2), or provide fire sprinklers.
Questions: patricia.shelton@tucsonaz.gov
03/12/2026 Residential Building REQUIRES RESUBMIT TC-RES-0326-01120
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2024 International Residential Code and 2018 International Energy Conservation Code. The 2024 International Energy Conservation Code takes effect July 1st. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2024 IRC with amendments and building ordinances for all dwellings.

Provide a separate response letter addressing each comment with location of change on the plans.

GENERAL COMMENTS:
https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Building-Codes

1. Plans submitted for a newly constructed one- or two-family dwelling after July 1, 2009 require a solar photo-voltaic system, or future installation preparation City of Tucson Ordinance #10549 .
a. Show a minimum 300 SF clear solar-ready zone on a roof or framing plan, T103.3.
b. Label a double breaker space for future Photo Voltaic on the panel schedule opposite end from the main/supply side, T103.9. Provide a future PV breaker space at the last breaker space on the electric panel schedule.
2. Show compliance with the Electric Vehicle Supply Equipment Ordinance adopted by the City of Tucson Ordinance #11844 on 6/22/2021. Include a 40 ampere 240-volt dedicated branch circuit with a NEMA 14-50R receptacle for charging an electric vehicle at a proposed parking space.

SITE PLAN:

1. Show the location of the electric service panel, R106.1.1. Show the location of sewer HCS coordinated with Pima County Wastewater, R106.1.1. https://www.pima.gov/1766/Wastewater-Reclamation Note the electrical line as underground unless overhead is approved by TEP. https://www.tep.com/construction-applications/#apply

PLANS:

1. Provide a minimum 6 mil polyethylene vapor retarder with joints lapped not less than 6 inches between the concrete floor slab and the base course or the prepared subgrade where a base course does not exist, R506.3.3.

SECTIONS - DETAILS:

1. Show one-hour fire-resistive framed construction separating dwellings in compliance with IBC Table 721.1(2). Extend the rated wall assembly to the roof sheathing.
2. Show exterior wood siding, sheathing, water-resistive barrier and wall framing with a 6” clearance above the ground (R317.1 item 5). Update detail #6 on sheet S.3.
3. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. Clarify the ceiling/roof insulation detail showing the air-impermeable rigid insulation material adhered to either side of the roof sheathing along with the batt insulation at keynote #11 on sheet A.4.
4. Show location and method of flashing all wall and roof intersections, R903.2.1.

MECHANICAL PLANS:

1. Show impact protection for appliances located in the garage, M1307.3.1.

ELECTRICAL PLANS:

1. Update the Riser Diagram showing a building service not exceeding 400 AMP or provide an electrical engineer’s fault current design with TEP coordination, NEC 225.30 and E3403.
2. Specify high-efficacy luminaires with an efficacy not less than 45 lumens per watt or lamps with efficacy not less than 65 lumens per watt (LED devices), N1104.1. Update note #4.
3. Include the Electric Vehicle load entry (typically 7680 watts) in the electrical load calculations (continuous demand) like the HVAC entry, N1104.2.2.
4. Show a surge-protective device (SPD) as an integral part of or placed immediately adjacent to the service equipment, E3606.5.
5. Either provide a vertical assembly listed for countertop (work surface) mounting, or a raceway terminated within the island cabinet for future assembly installation, E3901.4.
6. Provide GFCI protection for appliance receptacle outlets, E3902.12. Include:
1. Drinking water coolers
2. High pressure spray washing machines
3. Sump pumps
4. Dishwashers
5. Electric ranges
6. Wall-mounted ovens
7. Counter-mounted cooking units
8. Clothes dryers
9. Microwave ovens
7. Provide GFCI protection for receptacle outlets and HVAC equipment after September 1, 2026. E3902.14.

OUTDOOR LIGHTING CODE

1. Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3. Change the type “T” fixtures to full-cut-off.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

Please contact the plans reviewer if you have any questions:
Kenneth.VanKarsen@tucsonaz.gov
City of Tucson Residential Building Safety
03/09/2026 Residential Engineering REQUIRES RESUBMIT Permit: TC-RES-0326-01120
Location: 1250 S BEVERLY AV
Review Date: 3/9/2026
Site Engineering Comments:
1. For the site work, a separate permit called a Development Package (DP) is required. This can be applied for at TDC online. The approval of permit TC-RES-0326-01120 is dependent on the approval of the DP.
2. Per the City of Tucson Inclusive Home Design Ordinance (https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/inclusivehomedesignordinance.pdf, all new dwellings have a requirement to provide an “accessible route from public and common areas, including, but not limited to, a driveway or public street or sidewalk”. Draw, dimension, and label an accessible route from the driveway (or apron), sidewalk, or street to an accessible entrance. Ensure the route meets accessibility standards as articulated in 2017 ICC A117.1 Sections 402-403, including the minimum 4ft-width, slope and composition materials.
3. When the Development Package has been approved, re-submit a matching site plan to this permit for approval.
Corey Hines
Corey.Hines@TucsonAZ.gov
03/18/2026 Residential Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Erick Bieber
Planning & Development Services Department – Zoning Review Section

PROJECT: TC-RES-0326-01120
1250 S Beverly Ave, Tucson, AZ 85711
Residential New Dwelling (1st Review)

TRANSMITTAL DATE: March 18th, 2026

This site is located in the R-1 zone (UDC 4.7.8). A multifamily development is not a permitted use in the R-1 zone.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Correct plans, as noted in the comments below, along with a response letter indicating how all Site Zoning comments were addressed.

1. (Comment) The project proposes 6 residential units at 1250 S Beverly Ave. Per the Middle Housing Code Amendment, developments on sites with more than 4 residential units require a Development Package (DP). An associated DP for this project could not be located.

2. (Comment) 1250 S Beverly Ave is zoned R-1. A multifamily development is not a permitted use in the R-1 zone.

3. (Comment) The project description indicates a request for a change of zoning from R-1 to R-2 to accommodate multifamily development. Zoning is unable to locate a rezoning application for the site. A rezoning application submitted through Tucson Development Center Online is required to move forward with the rezoning process. Another pre-application conference will likely not be necessary to start the process as one has already been conducted under TP-PRE-0525-00097.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code

For questions regarding Zoning comments, please contact me at: Erick.Bieber@tucsonaz.gov
03/06/2026 PDSD Application Completeness Express REVIEW COMPLETED