Permit Number: TC-RES-0325-01550
Parcel: 126190710

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0325-01550
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2025 Site Engineering - Standard NOT REQUIRED
05/14/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/15/2025 Addressing Validation REQUIRES RESUBMIT The plans submitted appears to be for 2 Units. The address location does not have Units attached to the address. Unit #'s will have to be confirmed and assigned to Permit Application and on Plans prior to issuance. Once Zoning approves contact Pima County Addressing to resolve issue Addressing@pima.gov or 520-724-9512. Please sign into your TDC account and request a Change of Address and submit a Comment Letter and Plans (with unit #'s) on ALL plan sheets and any additional documents submitted.
05/08/2025 Residential Building - Standard REQUIRES RESUBMIT TC-RES-0325-01550

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments and building ordinances for all dwellings.

Each dwelling unit with kitchen requires a separate Pima County assigned street address after Zoning approval, R319. Show Pima County assigned unit numbers at each dwelling on the site plan. https://www.pima.gov/1010/Addressing-Frequently-Asked-Questions

An impact fee payment is required for each ADU at the time of permit payment.

Provide a response letter addressing each comment with location of change on the plans. Submit separate letter and plan set files.

GENERAL COMMENTS :

1. Show compliance with the Inclusive Home Design Ordinance adopted by the City of Tucson Ordinance #10463 on 10/16/2007. Notate accessible route, minimum door width, changes in floor elevation, door hardware, electrical outlet reach range, grab bar reinforcement, etc.
2. All plans submitted for a newly constructed one- or two-family dwelling after June 1, 2010, must provide gray water utilization or preparation, Ordinance #10579/11089 revised July 9, 2013. The ordinance revision now requires a gray drain line discharge from one fixture for a one-story dwelling. Additional gray fixture drains are optional. Show a second clothes washer standpipe plumbed to an exterior wall above grade when feasible. Use the appropriate detail at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Water-Energy-Conservation Gray Water Illustrations

SITE PLAN:

1. Each dwelling requires an appropriate location of electrical supply lines, R106.1.1. Identify the utility lines requiring upgrade or replacement.

PLANS:

1. Show a maximum ½” floor elevation changes at a notated accessible route entrance on the floor plan, R106.1.1. Include all threshold conditions for a route from the exterior into the living space.

PLUMBING PLANS:

1. The Tucson Water Department limits flow rates for the water meter size in compliance with P2903.7. Show an appropriate water meter size for the additional demand.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation with controlled exhaust, R303.4; N1103.6 & M1505.4. Identify the device model type providing an adjustable setting and note the minimum continuous setting or intermittent operation. A two or three-bedroom dwelling under 1501 SF requires a 45 CFM continuous setting.

ELECTRICAL PLANS:

1. TEP may require the service panel for the property at the closest building to the service transformer. A service line change or a new meter location must be coordinated with TEP for approval. Show an underground feeder from a metered service panel to the more distant dwelling.
2. Update the Riser Diagram for the close dwelling and the feeder size to the detached dwelling panel per TEP coordination, NEC 225.30 and E3403. Or show a minimum 8-foot clearance above the ADU roof for required overhead conductor clearance, E3604.2.1.
3. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

If you have any questions, please contact:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/pdsd
05/13/2025 Site Zoning - Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Krista Hansen
Planning & Development Services Department – Zoning Review Section

PROJECT: TC-RES-0325-01550, R-1
4327 E EASTLAND ST TUCSON, AZ 85711
Residential Addition (1st Review)

TRANSMITTAL DATE: 05/13/2025


This site is located in the R-1 zone (UDC 4.7.8). An accessory dwelling unit is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 6.6.3.

01. COMMENT: The permit description states, “Duplex Accessory Dwelling Units.” A duplex is not a permitted use in the R-1 zone (UDC Table 4.8.4). Remove any reference to duplex from the site plan.

02. COMMENT: Dimension the building height from design grade to the middle (between the eave and ridge) of the highest gable of the pitched roof (UDC 6.6.4).

03. COMMENT: Aerials show a shed along the western property line. Draw and dimension structure on site plan.

04. COMMENT: Excluding the ADUs, the minimum setback for the R-1 zone is 6’ or 2/3 the height of the wall, whichever is greater (Table 6.3-2.A). Draw, dimension, and label the actual setbacks of the existing structures (primary residence and storage shed) and the proposed structures to all property lines.

05. COMMENT: Draw, dimension, and label the vehicular use area, defined in the UDC as any area or structure used for the movement, parking, or standing of motor vehicles.

06. COMMENT: Provide total lot coverage calculation, which includes the vehicular use area(s). Porches (existing and proposed) are not included in lot coverage calculations (per UDC 6.4.3.C.1).

07. COMMENT: The parcel is approximately 8,520 square feet based on the lot dimensions provided. Correct square footage on site plan.

08. COMMENT: Per the Pima County information page, the legal description is “THOREAU LOT 27 BLK 1.” Add “BLK 1” to legal description on site plan.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code


RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Corrected plans, as noted in the comments below, along with a detailed letter indicating responses to the review comments.


For questions regarding Zoning comments, please contact me at: Krista.Hansen2@tucsonaz.gov
04/15/2025 PDSD Application Completeness Express REVIEW COMPLETED