Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2025 Site Engineering - Standard NOT REQUIRED
05/02/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/29/2025 Residential Building - Standard REQUIRES RESUBMIT TC-RES-0325-01522
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance. The plans require sufficient detail for demonstrating minimum building code compliance for passing all progress inspections.

Note the 2018 IRC reference on the plans.

Provide a response letter addressing each comment with location of change on the plans. Submit separate letter and plan set files.

SITE PLAN:

1. Each dwelling unit requires a Pima County assigned street address, R319. Show the appropriate unit number at each dwelling and on the site plan.

PLANS:

1. Clarify the extent of remodel or renovation on the plans, R106.1.1.

ELECTRICAL PLANS:

1. Show a smoke alarm in the bedroom and outside the doorway in the immediate vicinity with an electrical circuit, R314.3.
2. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2.
3. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3. Update circuit #5.
4. Show receptacle outlets at each kitchen counter space wider than 12” with no point along the wall line more than 24” from a receptacle outlet, E3901.4.1. Show receptacles within 2’ of counter edges or corners and no more than 4’ apart
5. Interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights, and smoke detectors require combination type arc-fault circuit interrupters, E3902.16. Add notation to plans.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
----------------------
05/02/2025 Site Zoning - Standard REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-RES-0325-01519, TC-RES-0325-01522
3539 S 8TH AV Units: 2 & 3 – R-2
Multifamily (1st Review)

TRANSMITTAL DATE: May 2, 2025

Provide a detailed comment response letter with your submittal that clearly shows how you have addressed all comments with your next submittal.

This site is located in the R-2 zone (UDC 4.7.9). A Multifamily is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10. Per TZ-CMP-0125-00003 letter dated 01/16/2025 This site is considered legal nonconforming for 3 dwelling units.

1. Based on aerial photographs there is a shed structure on the east side of units 2 & 3. Zoning was not able to find approved permit documents for these structures. Either 1) provide copies of the approved permit documents, 2) show these structures on the plan and provide applicable permit documents, or 3) show these structures on the plan as to be removed from the site.

2. Remove the parcel to the north from this plan.

3. Provide a lot coverage calculation on the plan that meets the requirements of UDC Article 6.4.3 and the example shown on the Residential Plot Plan Requirements found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Plan-Examples/Plot-Plan-Example.

4. Based on nonconforming letter, TZ-CMP-0125-00003, dated 1/16/2025, provide a note on the plan all mobile homes to be removed from site.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
04/07/2025 PDSD Application Completeness Express REVIEW COMPLETED