04/28/2025 Residential Building - Standard REQUIRES RESUBMIT TC-RES-0325-01482
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance. The plans require sufficient detail for demonstrating minimum building code compliance for passing all progress inspections.

Note the 2018 IRC reference on the plans.

The plans may require additional changes for showing 2018 IRC compliance of construction performed without a permit. Provide plans showing all changes after the last completed permit and proposed alterations.

Provide a response letter addressing each comment with location of change on the plans. Submit separate letter and plan set files.

Provide a clear and concise construction plan set. Sample drawings are available for understanding details. Sample plans at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits

SITE PLAN:

1. Show the location and size of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1. Identify the utility lines requiring upgrade or replacement. An overhead service conductor may not pass over the proposed building without an 8-foot clearance above the roof, E3604.2.1.
2. Clarify if a permitted building was altered or if the building was constructed without a permit, R106.1.1.
3. Show the location of the electrical subpanel, R106.1.1.

PLANS:

1. A structure may not extend to a point closer than 3 feet from the neighboring property line without fire rated protection for fire spread. Provide compliance with R302.1 (City of Tucson Amended) by including one-hour fire rated construction at the portion of structure placed within 3 feet of the property line in compliance with IBC Table 721.1(2).
2. Also, a roof projection (overhang beyond beam) may not extend closer than 24” to the adjoining (neighboring) property line. Remove any roof overhang along the neighboring property line.
3. Show the functional name of each room, R106.1.1.
4. Provide a Roof Framing Plan showing the rafters sized for supporting live and dead structural loads (Table R802.4.1(1)) or provide an engineer’s sealed plan set for manufactured trusses, R301.1.3.

SECTIONS - DETAILS:

1. Provide a wall section detail with (#4 rebar) reinforced 12” x 12” reinforced foundations for anchoring exterior framed (insulated) walls with pressure treated sills including ½” anchor bolts with 7” embedment, R403.1.6.
2. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5). The weep screed may extend with a minimum clearance 4” above grade or 2” above paved areas, R703.7.2.1.
3. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. Attic space outside of the thermal barrier requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2 or an unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Identify the ventilation requirements and insulation types for complying with the condensation control issues.

PLUMBING PLANS:

1. Show any plumbing in compliance with the 2018 IRC.

MECHANICAL PLANS:

1. Show the HVAC system size accordance with M1401.3, M1601.1.

ELECTRICAL PLANS:

1. Designate the circuit number at the location of each light fixture, receptacle, appliance, and equipment disconnect switch, R106.1.1.
2. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2.
3. Show at least one wall switch controlled light or outlet in bathrooms, hallways, stairways, attached garages, outdoor entrances or exits and all habitable rooms, E3903.3.
4. Interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights, and smoke detectors require combination type arc-fault circuit interrupters, E3902.16. Add notation to plans.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Show insulation and window values in compliance with, N1102.1.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits. Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
----------------------
04/30/2025 Site Zoning - Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: TC-RES-0325-01482
5075 S LAVENDER MOON WY. – C-1
Existing work out gym/office. located on back corner of my back yard (1st Review)

TRANSMITTAL DATE: April 30, 2025

This site is located in the C-1 zone (UDC 4.7.20). A single-family residence (SFR) is a permitted use in the zone (UDC Table 4.8-4).

1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Plan-Examples/Plot-Plan-Example.

2. Based on the description provided, Existing work out gym/office. located on back corner of my back yard, it is not clear what you are requesting to have permitted. It appears that you have two (2) structures, Gym & Ramada, that you need to permit. Clarify what you are requesting.

3. Additional comments maybe forthcoming once the required plot plan is provided.