Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING REVISION v.2
Permit Number - TC-RES-0325-01474
Review Name: RESIDENTIAL NEW DWELLING REVISION v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/25/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/25/2025 | Residential Building Standard | REQUIRES RESUBMIT | Update detail #1 on sheet S2.0 with an appropriate beam or provide a registrant stamp for the non-prescriptive design. Provide a complete roof framing plan with a ridge member sized with appropriate load carrying capacity. Show the ridge structural member as a full sized beam with appropriate load bearing rating when the roof pitch is less than 3” to 12”, R802.3. This is a 1:12 roof slope requiring a ridge beam rather than a ridge board. | ||
| 11/17/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |